The ultrasonic sensor is supplied with 24V DC via the brown connection wire. Blue is connected to ground. The 0-10V analogue value is output on the white wire.
Setting the limits
- Place the object at Position 1 (lower limit).
- Press T1 until both LEDs flash simultaneously (approximately 3 seconds).
- Both LEDs will flash alternately.
- Place the object at Position 2 (upper limit).
- Press T1 for about 1 second.
- The sensor returns to Normal Operating Mode.
Setting Rising/Falling Output Characteristic Curve:
- Press T1 until both LEDs flash alternately (approximately 13 seconds).
- LED D2 flashes.
- LED D1 indicates the output characteristic:
- On: Rising output characteristic.
- Off: Falling output characteristic.
- To change the output characteristic, press T1 for about 1 second.
- Wait for 10 seconds.
- The sensor returns to Normal Operating Mode.
Activating/Deactivating Teach-In:
- Turn OFF the power supply.
- While pressing T1, turn ON the power supply.
- Keep T1 pressed until both LEDs flash simultaneously (approximately 3 seconds).
- LED D2 flashes.
- LED D1 indicates the Teach-In status:
- On: Teach-In activated.
- Off: Teach-In deactivated.
- To activate or deactivate Teach-In, press T1 for about 1 second.
- Wait for 10 seconds.
- The sensor returns to Normal Operating Mode.
Resetting to Factory Settings:
- Turn OFF the power supply.
- While pressing T1, turn ON the power supply.
- Keep T1 pressed until both LEDs flash alternately (approximately 13 seconds).
- The sensor resets and returns to Normal Operating Mode.
More information can be found in the datasheet.