Hotel Lighting Controller

Hotel lighting controller for dimming, switching and RGB lighting

Table of Contents


Inputs

Abbreviation Summary Description Value Range
I1-20 Trigger input 1-20 for dimmer / switching input for digital circuits 0/1
S10 Trigger selection scene 10 Trigger selection lighting scene 10 0/1
S11 Trigger seletion scene 11 Trigger selection lighting scene 11 0/1
S12 Trigger seletion scene 12 Trigger selection lighting scene 12 0/1
S13 Trigger seletion scene 13 Trigger selection lighting scene 13 0/1
R Reset Reset input of the hotel lighting controller 0/1
IC Card switch 0/1
IS Service button Input service button
Depending on service mode
0/1
AIr Room state Status input
0 = 'Not booked'
1 = 'Booked'
2 = 'Guest checked in'
ID Door contact Input door contact 0/1
DisMo Disable motion sensor input Disable input of the motion sensor 0/1
Mo Motion sensor Motion sensor input 0/1
Dis Disable Disable-input of the hotel lighting controller 0/1




Outputs

Abbreviation Description Value Range
AQ1-20 Analog output of actuator/dimmer 1-20
on RGB - %-value red + %-value green * 1000 + %-value blue * 1000000
AQs Analogue Output - Value indicating currently active scene
QP Presence Output 0/1
QS Service Output 0/1
QD Service completed output 0/1
AQrm Analogue output for room service status
1 = Vacant/not cleaned
2 = Occupied/not cleaned
3 = Vacant/cleaned
4 = Occupied/cleaned




Parameters

Abbreviation Summary Description Unit Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
- 0/1 0
MS Service staff mode Input parameter - Service Staff mode
0 = Long click service button after inserting card
1 = Service button signal before inserting card
2 = Service button On before inserting card
3 = Card has to be inserted twice
- 2
TM Duration of Service Staff mode Parameter - Duration for Service Staff mode s 60
To Duration press and hold for 'All off' Parameter input duration long click for 'All off' s 2
Tl Timeout for leaving room Input parameter - Timeout for leaving the room
Enter 0 if no automatic off after leaving is to be triggered
s 60
M Max time between pulses Parameter - Maximum duration between 2 pulses s 0,35
SI Step Parameter - Step size for dimmer in % % 2
ST Step rate Parameter - Step rate for dimmer s 0,2
Min Minimum value Parameter input minimum dimmer value (0 to 50%) % 15
Max Maximum value Parameter input maximum dimmer value (50 to 100%) % 100
L Do not set last value Parameter - do not set last dimmer value (OFF = short click sets last value when switched off) - 0/1 0
TH Duration On Input parameter - Duration ON for motion sensor
Countdown starts from falling edge of Mo
s 180




Properties

Summary Description Default Value
Lighting scenes Lighting scene management -




Presence Simulation

This function block has a presence simulation.
Activate and define the presence simulation in the properties window: