Comfort Switch

Following a trigger, provides adjustable pulse at the output, includes permanent on and warning-function.
Before the output is deactivated again, a short switch off prewarning (on / off) takes place

Table of Contents


Inputs

Abbreviation Summary Description Value Range
Tg Toggle Pulse at input switches output (O) on for the duration set in parameter (Don). Another pulse switches output (O) off again.
Long-click = Switches output (O) permanently on.
0/1
Off Off Pulse: Outputs are reset / switched off.
On: Block is locked.
Dominating input.
The name of the connected sensor is used in the user interface.
0/1
On On Switches output (O) on. 0/1
DisPc Disable periphery control Disables all inputs when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
0/1




Outputs

Abbreviation Summary Description Value Range
O Output 0/1
AC API Connector Intelligent API based connector.
API Commands
-




Parameters

Abbreviation Summary Description Unit Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
- 0/1 0
Don On-duration of output (O) on pulse s 0...∞ 180
Tlc Time long-click for continious-on Defines the duration of a long click to permanently switch on the output (O) via the input (Tr). s 0...∞ 0,5
Tw Switch-off warning time Time of the switch-off warning before output (O) switches off. s 0...∞ 15
Dw Switch-off warning duration s 0...∞ 0,5




Timing Diagram


Presence Simulation

This function block has a presence simulation.
Activate and define the presence simulation in the properties window: