Long Click

Multiple function push-button with up to four functions, pulse after click

Table of Contents


Inputs

Abbreviation Summary Value Range
Tr Trigger 0/1
R Reset 0/1




Outputs

Abbreviation Summary Value Range
O1 Pulse when (Tr) ≤ (TI) 0/1
O2 Pulse when (TI) ≤ (Tr) ≤ 2x(TI) 0/1
O3 Pulse when 2x(TI) ≤ (Tr) ≤ 3x(TI) 0/1
O4 Pulse when 3x(TI) ≤ (Tr) 0/1
V Value (V1-4), depending on time of input (Tr)




Parameters

Abbreviation Summary Description Unit Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
- 0/1 0
TI Interval s 0...∞ 0,35
D Duration output pulse s 0...∞ 0,1
V1 Value 1 - 1
V2 Value 2 - 2
V3 Value 3 - 3
V4 Value 4 - 4




Timing Diagram