This function block will alert you of a fire or water leakage.
Table of Contents
Inputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
Ca | Confirm alarm | 0/1 | |
Cs | Confirm alarm signals | Deativates outputs Pas and Mas. Outputs Pa and Ma remain active. Assigned Audio Players or Lighting Controllers are also switched off. |
0/1 |
S | Smoke detector | Alarm input for external smoke detector. The name of the connected sensor is used in the user interface. |
0/1 |
W | Water detector | Alarm input for external water detector. The name of the connected sensor is used in the user interface. |
0/1 |
F | AFCI | Input for Arc-fault circuit interrupter. The name of the connected sensor is used in the user interface. |
0/1 |
T | Temperature input | Connection for external temperature sensors. The name of the connected sensor is used in the user interface. |
∞ |
Off | Off | Pulse: Outputs are reset / switched off. On: Block is locked. Dominating input. The name of the connected sensor is used in the user interface. |
0/1 |
Outputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
Pa | Pre-alarm | 0/1 | |
Ma | Main alarm | 0/1 | |
Pas | Pre-alarm signal | 0/1 | |
Mas | Main alarm signal | 0/1 | |
N | Number of active sensors | ∞ | |
At | Alarm test | 0/1 | |
Ca | Cause of alarm | Reports cause of the last alarm. | - |
Ta | Time and date of alarm | Reports date and time of the last alarm. | - |
AC | API Connector | Intelligent API based connector. API Commands |
- |
Parameters↑
Abbreviation | Summary | Description | Unit | Value Range | Default Value |
---|---|---|---|---|---|
Rem | Remanence input | Remanence input: If active, the function block retains its previous state after a Miniserver reboot. The state of the function block is saved: – When saving to the Miniserver – At a planned reboot – Before a backup – Once per hour – When activating/deactivating an alarm system (max. every 10s) The data is saved on the SD card. |
- | 0/1 | 0 |
Mad | Main alarm delay | Main alarm delay after activating the pre-alarm. | s | 0...∞ | 120 |
Maxϑ | Maximum temperature | If input (T) exceeds this value, the alarm will be activated. | ° | ∞ | 43 |
MaxA | Maximum alarm duration | The main alarm is automatically confirmed at the end of set time. If (Pac) = 1, the pre-alarm is also automatically confirmed. 0 = No duration limit |
s | 0...∞ | 300 |
Pac | Pre-alarm confirmation | 1 = Pre-alarm is confirmed automatically when (MaxA) is reached. 0 = Pre-alarm stays active when (MaxA) is reached. |
- | 0/1 | 0 |
Sm | Service mode | Enables the Service mode and suppresses the alarm, only (At) is activated in case of an alarm. 0 = Service mode off, 1 = Service mode permanently on, >1 = Service mode on for this time. |
s | 0...∞ | 0 |
Properties↑
Summary | Description | Value Range | Default Value |
---|---|---|---|
Number of messages | Maximum number of saved messages. | 2...100 | - |
Configuration | Configuration of the available inputs and outputs. | - | - |
Application↑
Loxone products, such as the Smoke Detector Air and Water Sensor Air, can simply be selected in the configuration dialog (double-click on block).
Function blocks such as audio players, lighting controllers, shading blocks or devices can be selected for audible and visual alarms (double-click on block).
Other third-party products can be connected to the dedicated inputs