Using the +/- input trigger sets an appropriate value at the output for EIB dimmer
Table of Contents
Inputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
+ | Dim+ | 0/1 | |
- | Dim- | 0/1 | |
DisPc | Disable periphery control | Disables all inputs. | 0/1 |
On | On | 0/1 | |
Off | Off | 0/1 | |
Set | Sets output (D) to value of input (Set) | ∞ | |
S | Status | Connect this input to a EIB-sensor (group address switching or response of switching) | 0/1 |
Cdv | Current dim value | Connect this input to a EIB-sensor (group address brightness or response of brightness) | ∞ |
Outputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
D | Dimmer output | Connect this output to a EIB-dimmer actuator (group address dimming) | ∞ |
S | Status | Switching output for turning On and Off dimmer This output is controlled by the inputs (On) and (Off). Connect this output to a EIB-dimming actuator (group address switching) |
0/1 |
Cdv | Current dim value | Connect this output to a EIB-dimming actuator (group address brightness). | ∞ |
AC | API Connector | Intelligent API based connector. API Commands |
- |
Parameters↑
Abbreviation | Summary | Value Range | Default Value |
---|---|---|---|
Sts | Step size | ∞ | 5 |
Rr | Repetition rate | ∞ | 0,2 |
EIB/KNX interface↑
The Loxone Miniserver Gen. 1 has a full-fledged EIB interface for a wide range of applications.
EIB sensors: Use of EIB sensors instead of classic buttons in a Loxone installation
User interface: Supplementing existing EIB installations for user interface
Logic: Supplementing existing EIB installations for logic
Presence Simulation↑
This function block has a presence simulation.
Activate and define the presence simulation in the properties window: