EIB push-button

On/Off push-button with trigger, central On/Off function

Table of Contents


Inputs

Abbreviation Summary Description Value Range
Tg Toggle Toggles between on and off. 0/1
Off Off Switches output (O) off.
Permanent 1 = Locks function block.
The name of the connected sensor is used in the user interface.
0/1
On On Switches output (O) on. 0/1
DisPc Disable periphery control Disables inputs (Tg), (Off), (On) when On. (e.g Child lock, cleaning) 0/1
S State This input can forward the status of a EIB-actuator to the output without triggering an action on the output. 0/1




Outputs

Abbreviation Summary Description Value Range
O Output Connect this output to an EIB-switching actuator (group address switching) 0/1
AC API Connector Intelligent API based connector.
API Commands
-




Parameters

Abbreviation Summary Description Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot.
The state of the function block is saved:
– When saving to the Miniserver
– At a planned reboot
– Before a backup
– Once per hour
The data is saved on the SD card.
0/1 0




EIB/KNX interface

The Loxone Miniserver Gen. 1 has a full-fledged EIB interface for a wide range of applications.

EIB sensors: Use of EIB sensors instead of classic buttons in a Loxone installation

User interface: Supplementing existing EIB installations for user interface

Logic: Supplementing existing EIB installations for logic