EIB Shading

EIB motor control for the blinds using two button control

Table of Contents


Inputs

Abbreviation Summary Description Unit Value Range
Po Partial open with push & hold - 0/1
Pc Partial close with push & hold - 0/1
Pos Position Used to provide feedback of the current shading position to the function block % 0...100
DisPc Disable periphery control Disables inputs Po, Pc, when On. (e.g Child lock, cleaning)
Control via user interface is still possible.
- 0/1




Outputs

Abbreviation Summary Description Value Range
Lo Long-term operation -1 = passive
0 = open
1 = close
Connect this output to an EIB-actuator (group address for long-term operation of blinds)
So Short-term operation -1 = passive
0 = open
1 = close
Connect this output to an EIB-actuator (group address for short-term operation of blinds)
Pos Position of shading
AC API Connector Intelligent API based connector.
API Commands
-




Parameters

Abbreviation Summary Description Unit Value Range Default Value
Tlc Time long-click Pulse duration on inputs (Po) (Pc) to trigger a long-term operation (Lo). s 0...∞ 0,3