Mounting

Install the device in a suitable installation box.

Connect the power supply (orange/white terminal).

Connect the orange MP-Bus lead to the MP-Bus nodes. The GND of the MP-Bus nodes must be connected to the GND of the Belimo Air.

While 24VAC power supply is possible for many MP-Bus devices, the Belimo Air can only be supplied with 24VDC.


Commissioning

In delivery state, pairing mode will be active after the power supply has been established. This is indicated by the status LED flashing red/green/orange.

Then follow the pairing procedure on the Air Interface.

To activate the pairing mode manually, switch off the power for 10 seconds, then switch it back on. If no connection to a Miniserver can be established for two minutes, then pairing mode is activated for 30 minutes.


Commissioning Belimo devices

There are 3 ways to insert Belimo devices:

Belimo Datapool devices are added in the following steps:
1. Download suitable template for device from Loxone Library
2. Import template
3. Insert template into programming:

Then configure / address the inserted Belimo device:

If Belimo devices are addressed via the Belimo App, their address and serial number is entered in the properties:

For more information, please visit the Belimo Documentation.


Limitation of inputs/outputs

The number of usable inputs/outputs (IOs) is limited to 128 IOs in total per Belimo Tree/Air and to 20 IOs per Belimo device. Only IOs that are actually used on a programming page are relevant for this.

If these numbers are exceeded, an error message is displayed when inserting further IOs.

To solve this, IOs that are not absolutely required can be removed from the programming. Alternatively, use an additional Belimo Tree/Air.


Data Reading

Only the values that are actually sent to the Miniserver are displayed in the Belimo Monitor.

This means that only values that have changed are shown. The data is not displayed in the monitor with every polling cycle.


Diagnostic Inputs

Summary Description Unit Value Range
Online Status Belimo Air Indicates whether the device can be reached by the Miniserver.
Diagnostics for Air devices
Diagnostics for Tree devices
Diagnostics for Extensions
Digital 0/1




Properties

Summary Description Unit Value Range Default Value
Monitor online status When selected, you will be notified via System Status or the Mailer if the device is no longer available or goes offline. - - -
Serial number Serial number of Air device - - -
Device type Air device type - - -
MP-Bus Supply Specifies if MP-Bus supply is active - - -
Device Status Update Cycle Belimo device specific status update cycle time in seconds (10 - 600) s 10...600 60




Documents

Datasheet Belimo Air

Inputs, outputs, status values and error messages




Inputs, outputs, status values and error messages