Optimised dimmer with double click function for single button operation.
Table of Contents
Inputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
Tg | Toggle | Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1). Long-click for dimming up/down. |
0/1 |
+ | Dim+ | Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1). Long-click for dimming up. |
0/1 |
- | Dim- | Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1). Long-click for dimming down. |
0/1 |
Off | Off | Pulse: Outputs are reset / switched off. On: Block is locked. Dominating input. The name of the connected sensor is used in the user interface. |
0/1 |
DisPc | Disable periphery control | Disables inputs (Tg), (+), (-) when On. (e.g Child lock, cleaning) Control via user interface is still possible. |
0/1 |
Set | Sets output (D) to value of input (Set) | ∞ |
Outputs↑
Abbreviation | Summary | Description | Value Range |
---|---|---|---|
D | Dimmer output | Analog output for dimmer control (e.g. 0-10V) | ∞ |
S | Status | On when output (D) is greater than 0. | 0/1 |
AC | API Connector | Intelligent API based connector. API Commands |
- |
Parameters↑
Abbreviation | Summary | Description | Value Range | Default Value |
---|---|---|---|---|
Rem | Remanence input | Remanence input: If active, the function block retains its previous state after a Miniserver reboot. The state of the function block is saved: – When saving to the Miniserver – At a planned reboot – Before a backup – Once per hour The data is saved on the SD card. |
0/1 | 0 |
Di | Delay input | Delays input for set time. Applies to inputs (Tg), (+), (-). |
∞ | 0,4 |
Sts | Step size | ∞ | 0,5 | |
Str | Step rate | Dim value is in-/decreased by (Sts) every (Str) seconds on long-click. | ∞ | 0,2 |
MinD | Minimum dim value | ∞ | 0 | |
MaxD | Maximum dim value | ∞ | 100 | |
Dm | Dim mode | 1 = Dim between parameters (MinD) and (MaxD) on long-click. 0 = Stop dimming when reaching parameter (MinD) or parameter (MaxD) on long-click. Only applies to input (Tg). |
0/1 | 0 |
Lv | Last value | 1 = Sets output (D) to (MaxD) when switching on. 0 = Sets last value to ouput (D) when switching on. |
0/1 | 0 |
Presence Simulation↑
This function block has a presence simulation.
Activate and define the presence simulation in the properties window: